LK Armatur Our websites English
Close

Our websites

50B Strainer

50B Strainer

Dirt filter 50B is used in heating and cooling systems.

50B Strainer

Variants

50B - Female thread

50B - Female thread 4 variants

Article Dim. Kvs m³/h A mm B mm Weight (kg) Dimensional sketch Item List
506 40 90 M ⅜" 2,4 50 36 0.1
506 40 91 M ½" 3,1 53 36 0.1
506 40 92 M ¾" 5,1 65 43 0.2
506 40 93 M 1" 77 54 0.3

506 40 90

Dim. M ⅜"
Kvs m³/h 2,4
A mm 50
B mm 36
Weight (kg) 0.1
Dimensional sketch
Item list

506 40 91

Dim. M ½"
Kvs m³/h 3,1
A mm 53
B mm 36
Weight (kg) 0.1
Dimensional sketch
Item list

506 40 92

Dim. M ¾"
Kvs m³/h 5,1
A mm 65
B mm 43
Weight (kg) 0.2
Dimensional sketch
Item list

506 40 93

Dim. M 1"
Kvs m³/h
A mm 77
B mm 54
Weight (kg) 0.3
Dimensional sketch
Item list

Detailed Information

Description

Dirt filter 50B is used in heating and cooling systems.

The arrow on the filter housing indicates the direction of flow. The best function is achieved when the dirt filter is installed horizontally with the filter drum facing down. The dirt filter must be fitted in a zone that can be closed. This is because it must be possible to easily collect water flowing out when cleaning the filter, while also avoiding unnecessary topping-up of the water in the system.

The filter should be cleaned according to a set procedure. On installation, the filter is ideally cleaned after just a month or so of operating time. The time interval can then be extended depending on the degree of contamination in the filter. If necessary, use standard washing-up liquid or a soap solution to clean the filter drum.

Technical Data

Working temperature: Max. 150 °C
Max. working pressure: 1.6 MPa
Thread standard: G - female thread
Other data: Material, dirt filter Brass MS58 (**=Red Brass)
Material, filter drum Stainless steel SS 2331-02
Other data: Specification filter cartridge:
Number of holes/cm² 240 st
Hole area 0,10 mm²
Mesh opening, filter Ø max. 0,3 mm
Material, cover sealing: Viton