LK Armatur Our websites English
Close

Our websites

LK HydronicGroup 90C

LK HydronicGroup 90C

  • Adapted for cooling
  • Easy to install
  • Easy to combine with electronic regulation

LK HydronicGroup is a complete pump group that is suitable for cooling systems where mixed supply is desirable.

LK HydronicGroup 90C

Variants

LK 90C - Pump group for passive cooling

LK 90C - Pump group for passive cooling 1 artikel

Article Dim. Kvs m³/h Note Weight (kg) Item List
299387 F 1" x M 1" 6,3 /10,0 Wilo PARA 15-130/8-75/SC-9 4.0

299387

Dim. F 1" x M 1"
Kvs m³/h 6,3 /10,0
Note Wilo PARA 15-130/8-75/SC-9
Weight (kg) 4.0
Item list

Detailed Information

Description

LK HydronicGroup is a complete pump group that is suitable for cooling systems where mixed supply is desirable.

By running the brine in the collector hose to a fan coil, you can cool your home with the cold naturally found in the ground. In addition, the borehole is recharged during the summer, which increases the performance of the heat pump.

HydronicGroup 90C is suitable to combine with the LK 322 CoolUnit which ensures the liquid is run in the right direction.

LK HydronicGroup comprises a high efficient circulation pump, insulation, wall mounting bracket and two ball valves with thermometer. In the model where mixed supply is desired, a three-way mixing valve is included.

Technical Data

Voltage: 230 VAC 50/60 Hz
Power consumption: 10-75 W, depending on pump speed
Working temperature: Min. -15 °C/Max. 100 °C
Supply temperature: Min. 5 °C
Ambient temperature: Min. 5 °C/Max. 58 °C
Max. working pressure: 1.0 MPa (10 bar)
Leakage: < 0,2% of Kvs at 100 kPa
Media 1: Water - Glycol mixture max. 50%
Thread standard: Rp - female thread
Circulating pumps: Wilo Para 15-130/8-75/SC-9
Material, valve body: Brass EN 12165 CW617N
Other data: Cooling efficiency: 7 kW (ΔT 10 °C 10 l/min.)

Application

PUMP GROUP FOR PASSIVE COOLING

Technical Diagrams

Capacity Diagram